Skip to content Skip to footer

NovaCool RDHx

The name NovaCool embodies our commitment to cutting-edge cooling technology and energy efficiency, symbolizing a new star in the industry. Inspired by “Inova,” NovaCool represents innovation and excellence, setting a bright standard for the future of cooling solutions.

NovaCool RDHx delivers up to 85kW of cooling in a compact footprint, expertly handling high-temperature inlet water to boost free cooling and slash costs. Tool-free, hot-swappable EC fans (N+1 redundancy), dual power feeds with built-in ATS, and a standard leakage sensor streamline maintenance and safety. Rigorously tested by an external lab, it surpasses theoretical specs while offering best-in-class lead times—making it the ideal solution for high-density environments.

Product Key Features

Maximum Cooling Duty

Maximum cooling duty up to 85kW @ 20°C water inlet and air supply @ 24°C

Available Sizes

Available in 600 mm and 800 mm width and 42RU, 48RU, and 52RU height

Efficient Design

High-efficiency heat exchanger with a unique design

Reliable Power

Dual Power feed with Inbuilt ATS

Easy Installation

Toolless mounting of fans and controller

Hot Swap Capability

Hot swappable EC fans with N+1 redundant

Leak Protection

Standard leakage sensor that automatically shuts off the water supply in case of a leak alarm, ensuring server safety

Safe Isolation

Flexible hoses are isolated from the IT equipment

Accessible Service

Controller can be serviced while door remain closed

Universal Fit

Compatible to all Industry Standard OEM Rack

Why Inova NovaCool RDHx?

Maximum Cooling, Minimal Footprint

High cooling capacity delivered in a compact, space-saving design.

Speedy ROI, Lower Operating Costs

Rapid return on investment and reduced total cost of ownership.

Unlock Free Cooling Potential

Effective management of high-temperature inlet water to capitalize on free cooling opportunities.

Tool-Free Maintenance & Flexibility

Hot-swappable fans and controllers for effortless upkeep and configuration changes.

Proven Performance, Lab-Certified

Guaranteed results validated by external testing-beyond theopretical coil specs.

Industry-Leading Delivery Times

Accelerated lead times to get you up and running faster than the competition.

Edit Content
Model 42U and 45U 48U and 52U
600W 800W 600W 800W
NC1-642W NC1-842W NC1-648W NC1-848W
Total Cooling Capacity 60kW* 85kW*
Height mm(") 2050 (80.7) 2330 (91.7)
Width mm(") 598 (23.5) 798 (31.4) 598 (23.5) 798 (31.4)
Depth mm(") 380 (14.96)
Dry Weight Kg (lbs) 152 (334) 156 (343) 170 (374) 186 (410)
Wet Weight Kg (lbs) 165 (363) 169 (372) 185 (407) 204 (449)
Pipe Connection Top/Bottom – 25mm (1") with BSP or NPT
Voltage range 200-240V & 50/60Hz
Max Power Draw W 844 1013
Communication Protocol Modbus TCP IP (Std), BACnet (opt)

* Conditions for rated capacity supply water temperature @20°C (68°F)/return warm water temperature @30°C(86°F) and air supply temperature @24°C (75.2°F)

Edit Content
Catalog
NovaCool RDHx CAT_NovaCool RDHx_V1.1.pdf

Can’t find what you need?

Contact sales@inovadc.com for more information.